DESCRIPTION RANGE UNITS DEFAULT VALUE
Motor TempOverride 150 to 200
(66 to 93) DEG F
(DEG C) 200
(93)
Cond Pressure Override 90 to 200 (620 to 1379) psig
(kPa) 125 (862)
Refrig Override Delta T 2to5
(1 to 3) DEG F
(DEG C) 3
(1.6)
Chilled Medium Water/Brine Water
Brine Refrig Trippoint 8to40
(–13.3 to 4) DEG F
(DEG C) 33
(1)
Compr Discharge Alert 125 to 200
(52 to 93) DEG F
(DEG C) 200
(93)
Bearing TempAlert 165 to 210
(74 to 99) DEG F
(DEG C) 210
(99)
Water Flow VerifyTime 0.5 to 5 MIN 5
Oil Press VerifyTime 15 to 300 SEC 15
Water/Brine Deadband 0.5 to 2.0
(0.3 to 1.1) DEG F
(DEG C) 1.0
(0.6)
Recycle Restart Delta T 2.0 to 10
(1.1 to 5.5) DEG F
(DEG C) 5
(2.8)
Recycle Shutdown Delta T 0.5 to 4.0
(0.27 to 2.2) DEGF
(DEG C) 1.0
(0.6)
Surge Limit/HGBP Option
Surge=0/HGBP=1 0/1 0
Surge/HGBP Delta T1 0.5 to 15
(0.3 to 8.3) DEG F
(DEG C) 1.5
(0.8)
Surge/HGBP Delta P1 30 to 170 (206 to 1172) psi
(kPa) 50 (345)
Surge/HGBP Delta T2 0.5 to 15.0
(0.3 to 8.3) DEG F
(DEG C) 10
(5.6)
Surge/HGBP Delta P2 30 to 170 (206 to 1172) psi
(kPa) 85 (586)
Surge/HGBP Deadband 1to3
(0.6 to 1.6) DEG F
(DEG C) 1
(0.6)
Surge Delta Percent Amps 10to 50 % 25
Surge Time Period 1to5 MIN 2
Demand Limit Source
Amps=0/Load=1 0/1 0
Amps Correction Factor 1to8 3