Example 6 — Lead/Lag Co nfi guration Display S cre en

To access this display f ro m the LID default screen:

1. Press MENU.
2. Press SERVICE.

3. Scroll down to highlight EQUIPMENT CONFIGURATION.

4. Press SELECT.

5. Scroll down to highlight Lead/Lag.

6. Press SELECT.

Table 2, Example 6 — Lead/Lag Configuration Screen

Description Configurable

Range Units Reference

Point Name Default

Value
LEAD/LAG SELECT
DISABLE =0, LE AD =1,
LAG =2, STANDBY =3
Load Balance O ption
Common Sensor Option
LAG Percent Capacity
LAG Address
LAG START Time r
LAG STOP Timer
PRESTART FAULT Timer
STANDBY Chiller Option
STANDBY Percent Capacity
STANDBY Address
0-3
DISABLE/ENABLE
DISABLE/ENABLE
25-75
1-236
2-60
2-60
0-30
DISABLE/ENABLE
25-75
1-236
%
MIN
MIN
MIN
%
leadlag
loadbal
commsens
lag per
lag add
lagstart
lagstop
preflt
stndopt
stnd per
stnd add
0
DISABLE
DISABLE
50
92
10
10
15
DISABLE
50
93