Example 5 — Configurat i on (Config) Display Sc ree n

To access this display f ro m the LID default screen:

1. Press MENU.
2. Press SERVICE.

3. Scroll down to highlight EQUIPMENT CONFIGURATION.

4. Press SELECT.

5. Scroll down to highlight CONFIG.

6. Press SELECT.

Note: = delta degrees.

Table 2, Example 5 — Configuration (Config) Display Screen

Description Configurable

Range Units Reference

Point Name Default

Value
RESET TYPE 1
Degrees Reset at 20 mA
RESET TYPE 2
Remote Temp (No Reset)
Remote Temp (Full Reset)
Degrees Reset
RESET TYPE 3
CHW Delta T (No Reset )
CHW Delta T (Full Reset)
Degrees Reset
Select/Enable Reset T ype
ECW CONTROL OPTION
Demand Limit At 20 mA
20mA Demand Lim it Option
Auto Restart Option
Remote Contacts Option
Temp Pulldown Deg/Min
Load Pulldown %/Min
Select Ramp Type:
Temp = 0, Load = 1
Loadshed Group Number
Loadshed Demand Delta
Maximum Loadsh ed Tim e
CCN Occupancy Config:
Schedule Number
Broadcast Option
ICE BUILD Option
ICE BUILD TERMINATION
0 =Temp, 1 =Contacts, 2 =Both
ICE BUILD Recycle Optio n
–30-30 (–17-17)
–40-245 (–40-118)
–40-245 (–40-118)
–30-30 (–17-17)
0-15 (0-8)
0-15 (0-8)
–30-30 (–17-17)
0-3
DISABLE/ENABLE
40-100
DISABLE/ENABLE
DISABLE/ENABLE
DISABLE/ENABLE
2-10
5-20
0/1
0-99
0-60
0-120
3-99
DISABLE/ENABLE
DISABLE/ENABLE
0-2
DISABLE/ENABLE
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
DEG F (DEG C)
%
%
MIN
deg 20mA
res rt1
res rt2
res rt
restd 1
restd 2
deg chw
res sel
ecw opt
dem 20ma
dem sel
astart
r contact
tmp ramp
kw ramp
ramp opt
ldsgrp
ldsdelta
maxldstm
occpcxxe
occbrcst
ibopt
ibterm
ibrecyc
10(6)
85 (29)
65 (18)
10(6)
10(6)
0(0)
5(3)
0
DISABLE
40
DISABLE
DISABLE
DISABLE
3
10
1
0
20
60
3
DISABLE
DISABLE
0
DISABLE