Rack-mounting the components Page 75 of 488

component. Consult the manufacturer’s documentation for the weight of other components installed during the CS 1000E system installation.

Table 11

Weight of CS 1000E system components

Component

Lbs

Kg

 

 

 

CS 1000E Call Server

29

13.2

 

 

 

Signaling Server

23

10.5

 

 

 

Media Gateway without cards

 

 

with 4 cards

26

12

 

 

30

13.5

 

 

 

Media Gateway Expander

 

 

without cards

26

12

with 4 cards

30

13.5

 

 

 

BayStack 470 Switch

14.7

6.7

 

 

 

BayStack 460 Power over Ethernet Switch

12.76

5.8

 

 

 

MRV Terminal Server

11

5

 

 

 

 

Guidelines for component placement in a rack

When installing equipment, the Layer two switches should be in a central location to allow for easy access of all LAN cabling. The Media Gateways and Media Gateway Expanders must be mounted together vertically, and they must be powered from the same power rail. Typical vertical power bars in equipment racks are rated at 15/20 amps @ 120 volts. Ensure that the equipment load does not exceed the power bar rating. Refer to Communication Server 1000E: Planning and Engineering (553-3041-120) for information on power consumption. Do not place redundant equipment on the same electrical circuit.

There are no thermal concerns about equipment placement.