Table 2 — LID Screens

Notes:
1. Only 12 lines of information appear on the LID screen at any given time. Press NEXT or PREVIOUS to
highlight a point or to view points below or above the current screen.
2. The LID may be configured in English or SI units, as required, through the LID configuration screen.
3. Data appearing in the Re ference Point Names co lum n is used for CCN operations on ly.
Example 1 — Status01 Dis pl ay Screen
To access this display from the LID default screen:
1. Press MENU.
2. Press STATUS (STATUS01 will be highligh ted).
3. Press SELECT.
Table 2, Exa mple 1 — Statu s01 Display Screen
Description Range Units Reference Point
Name (Alarm
History)
Control Mode
Run Status
Occupied ?
Alarm State
*Chiller Start/Stop
Base Demand Limit
*Active Demand Limit
Compressor Motor Load
Current
Amps
*Target Guide Vane Pos
Actual Guide Vane Pos
Water/Brine: Setpo int
* Control Point
Reset.Off.Local.CCN
Timeout.Recycle.Startup.
Ramping.Running.Demand .
Override.Shutdown.Abnorm al.
Pumpdown
No/Yes
NORMAL/ALARM
STOP/START
40-100
40-100
0-999
0-999
0-9999
0-100
0-100
10-120 (–12.2-48.9)
10-120 (–12.2-48.9)
%
%
%
%
AMPS
%
%
DEG F (DEG C)
DEG F (DEG C)
MODE
STATUS
OCC
ALM
CHIL S S
DLM
DEM LIM
CA L
CA P
CA A
GV TRG
GV ACT
SP
LCW STPT