Section 2

1010NFM-3J

 

 

 

NOTE: Using the <F1> key (Totalizer clear command) also clears all channel totalizers plus the overflow register described in the last paragraph.

Assigning Relay 1 and 2 Functions

System 1010N, depending on the model, provides at least two alarm relays. Please refer to the Hard- ware Installation Drawing for wiring details. Relays respond to any of the alarm conditions/data func- tions included on the Relay Option List.

 

RELAY OPTION LIST

Not Used

Not Active

Power Off

Power Off alarm occurs when power fails

S.G.

Specific Gravity value relay trip-point

 

 

 

Hi Temperature

High temperature value relay trip-point

 

 

 

Low Temperature

Low temperature value relay trip-point

High Flow

Flow rate exceeds high flow setpoint

Low Flow

Flow rate falls below low flow setpoint

 

 

 

Flow Alarm

Flow rate exceeds or falls below flow setpoints

Fault Alarm

System loses receive signal

 

 

 

Spacing

Transducer spacing needs adjusting

 

 

 

Empty

Empty pipe alarm

Aeration

Aeration percentage exceeds alarm setpoint

 

 

 

Reverse Flow

Flow is in negative direction

BatchTot

Batch/Sample total advances

 

Interface

Liquid interface setpoint exceeded

Pos Total

Positive total volume advances by 1 digit

 

Neg Total

Negative total volume advances by 1 digit

Soft Fault

Fault condition - memory mode active

To assign functions to Relay 1:

To access the [Relay] option list press

To move the cursor to the desired Relay assignment press

To store selection press ENT . Repeat procedure for Relay 2.

2.10.3ANALOG INPUT SETUP (optional function)

The Analog Input Setup function assigns an active analog input to a measurement channel/path. The meter provides four DC current input ports for single and Dual Channel units. The DC current input ranges from a zero level of 4 mA to a full scale of 20 mA. The [Analog Input Setup] menu cell allows you to enable this port and then span it to any desired scaling.

For example, when using the analog input viscosity function the numeric variables might be spanned as follows: 4mA=1 (water) and 20mA=100 (more viscous liquid). This spanning configuration allows the meter to use this constant numerical change to improve calibration in real time. The various flow- meter models allow you to associate the analog input to active system variables such as specific gravity, viscosity and others (see table on next page).

2-61

Page 101
Image 101
Siemens SITRANS FUS1010 NEMA-4X/ IP 65 manual Relay Option List, Analog Input Setup optional function