Section 2

1010NFM-3J

 

 

 

NOTE: An Alarm Event report will be generated immediately after the transition from a non- alarm to an alarm event. The reverse situation (alarm state to non-alarm state) does not trigger the event-based Datalogger.

Event-based Datalogger messages conserve memory. However, if you use this feature to monitor a level such as Flow Alarm, set the alarm threshold high enough to avoid repetitive triggering. You must select Site ID (Name) and Time to “time-stamp” the alarm events. Note that on the Datalogger report, a [-] represents a reserved letter code space (inactive alarm) and a letter code represents an active alarm.

To select Datalogger Event items:

To access the [Datalogger Events] option list press

. Move cursor to desired item by

pressing

then press ENT to select it. Note that a plus sign(+) appears before the

item.

 

 

To de-select Datalogger Events:

To move the cursor to the item press sign (+) from the item.

thenCLR. Note that this removes the plus

After selecting all desired items press to leave the [Datalogger Events] option list.

2.9.5 DISPLAY DATALOGGER

Use this menu cell to enable and format the on-screen datalogger. You can allow the report to scroll on the screen with or without line wrapping. Selecting line wrap, forces a line feed after approximately 40 characters. This command is effective only after you select data items and the Datalogger has accu- mulated some data.

To enable the on-screen datalogger display:

To access the [Display Datalogger] option list press

Move the cursor to the desired function.

To invoke the function press ENT

To scroll the on-screen datalogger display:

To display one line at a time press

Use

+ key to scroll down one screen (10 lines) at a time.

Use

= key to jump to 15 lines of the last screen.

In No Line Wrap mode:

Useor to scroll one column to the left or right. Use ALT + or ALT+

To scroll 8 columns to the right or the left. To get out of the display, press MENU

2-56