Siemens SITRANS FUS1010 NEMA-4X/ IP 65 manual Flowmeter Setup

Models: SITRANS FUS1010 NEMA-4X/ IP 65

1 232
Download 232 pages 51.98 Kb
Page 7
Image 7

Manual Addendum

1010FMA-4

2.2Flowmeter Setup

NOTE: The following instructions require the use of the keypad and the menu. The installer should become familiar with their use before proceeding further.

2.2.1Switch the flowmeter on. Press the <MENU> key.

2.2.2On multi-channel flowmeters, use the arrow keys to select [Dual Channel Flow] or [Dual Beam Flow] depending on the mode utilized for the wet-flow calibration.

2.2.3Use the arrow keys to select either [Clamp-on], [Flow Tube] or [Clamp-on Spool].

2.2.4Select [Full Site Setup] and use the <Right Arrow> to select [Channel Setup]; then select [Recall Site Setup].

2.2.5Use the <Down Arrow> to scroll to the site name indicated on the Calibration Diagnos- tic Data Sheet. Then press <ENT>.

2.2.6The meter will perform a momentary “Makeup” routine that will take a few seconds and then begin operation.

2.2.7Refer to your 1010 field manual for instructions on setting zero flow.

NOTE: Setting zero flow must be performed each time the transducers are installed. The zero adjustment has no effect on the wet-flow calibration data or the cali- bration (Kc) factor.

2.2.8Using the arrow keys, scroll to the Data Span/Set/Cal menu location. Verify that the [Kc] (calibration) factor matches the value indicated on the diagnostic data sheet.

2.2.9If you are measuring a liquid other than ambient water, select the [Liquid Class] menu cell and <Down Arrow> from there to [Viscosity]. Enter the correct viscosity for the liquid you will be monitoring.

2.2.10Setup is now complete. Press the <MENU> key twice to view the flow rate display. DO NOT utilize the [Save Site] command when it appears.

2.2.11When measurements are completed, simply turn off the meter. DO NOT save the site. This might contaminate the wet-flow calibration data already stored.

NOTE: Contact Siemens’ Technical Services Department if any flow calibration data is accidentally removed or overwritten.