Section 2

1010NFM-3J

 

 

 

High Flow

The [High Flow Alarm] menu cell allows you to set the HI Alarm relay trip-point and the position of the HI Alarm cursor on the Stripchart Display. The entered value must fall within the volumetric flow (Vfo) analog span for the HI Alarm cursor to appear on the Graphic Screen.

To set the High Flow Alarm:

To activate numeric entry press

Use numeric keys to type the High Flow Alarm setpoint in the selected flow rate units. To store data press ENT

Low Flow

The[ Low Flow] menu cell allows you to set the LO Alarm relay trip-point and position of the LO Alarm cursor on the Stripchart Display. The entered value must fall within the volumetric flow (Vfo) analog span for the Low Alarm cursor to appear on the Graphic Screen.

To set the Low Flow Alarm:

To activate numeric entry press

Use the numeric keys to type the Low Flow alarm setpoint. To store data press ENT

The following Alarm Relay Setpoints are set in the same way as the two previously shown examples by entering numeric values and storing the data.

High S.G.

This selection sets the High S.G. alarm function the specific gravity of a selected liquid.

Low S.G.

This selection sets the Low S.G. alarm function the specific gravity of a selected liquid.

High Viscosity cS

The [High Viscosity cS] menu cell sets the high liquid viscosity alarm relay setpoint. The viscosity units are centistokes with no alternatives offered.

Low Viscosity cS

The [Low Viscosity cS] menu cell sets the low liquid viscosity alarm relay setpoint. The viscosity units are centistokes with no alternatives offered.

High Temperature

The [High Temperature] menu cell sets the high temperature alarm relay setpoint. If metric preferences are selected prior to site creation the temperature units will be in Centigrade. If English preferences are selected prior to site creation the temperature units will be in Fahrenheit.

Low Temperature

The [Low Temperature] menu cell sets the low temperature alarm relay setpoint If metric preferences are selected prior to site creation the temperature units will be in Centigrade. If English preferences are selected prior to site creation the temperature units will be in Fahrenheit.