Infeed

1.1 Active Infeed

1.1.2Active Infeed closed-loop control Booksize

Schematic structure

%RRNVL]H

&RQWURO8QLW

)LUPZDUH

$FWLYH

,QIHHG 0DQLSXODWHGYDULDEOHV $FWXDOYDOXHV

'5,9(&/L4

6XSSO\V\VWHP

0DLQVZLWFK

)XVHV

/LQHFRQWDFWRU RSWLRQDO

9ROWDJH6HQVLQJ

0RGXOH RSWLRQDO $FWXDO YDOXHV

/LQHILOWHU RSWLRQDO

/LQHUHDFWRU $FWLYH,QWHUIDFH

0RGXOH7HPSHUDWXUHIRU $FWLYH,QWHUIDFH 0RGXOHV

$FWLYH/LQH0RGXOH

'&OLQN

Figure 1-1 Schematic structure of Active Infeed Booksize

Active Infeed closed-loop control for Active Line Modules Booksize

The Active Line Module can be operated in two different modes depending on the parameterized line supply voltage (p0210):

Active Mode

In Active Mode, the DC link voltage is regulated to a variable setpoint (p3510), which results in a sinusoidal line current (cosφ = 1). The level of the reactive current is also controlled and can be specifically defined.

Smart Mode

Energy recovery capability is maintained in Smart Mode, although there is a lower DC link voltage in comparison to the Active Mode. The DC link voltage is dependent on the current line voltage.

The DC link voltage setpoint (p3510) and the control type are preset as follows during commissioning in line with the connection voltage (p0210):

Table 1-1

Presetting the control type and DC link voltage booksize

 

 

 

 

 

 

 

 

 

Supply voltage p0210 [V]

380-400

401-415

416-440

460

480

Control type p3400.0

"0" = Active Mode

"1" = Smart Mode

 

Vdc_soll p3510 [V]

600

625

562-5941)

6211)

6481)

22

Drive Functions

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Page 22
Image 22
Efficient Networks S120 manual Active Infeed closed-loop control Booksize, Schematic structure, Infeed Active Infeed