Communication PROFIBUS DP/PROFINET IO 10.1 Communications according to PROFIdrive

Bit

Meaning

 

Comments

BICO

 

Note:

 

 

 

 

The message is parameterized as follows:

 

 

 

p2155 Threshold value

 

 

 

 

p2140 Hysteresis

 

 

 

 

Application:

 

 

 

 

Speed monitoring.

 

 

 

4

Reserved

1

 

 

0

-

 

5

Reserved

1

-

 

 

0

 

6

No motor overtemperature alarm

1

No motor overtemperature alarm

BO: r2135.14

 

 

 

The temperature of the motor is within the

(inverted)

 

 

 

permissible range.

 

 

 

0

Alarm, motor overtemperature

 

 

 

 

The temperature of the motor is greater than the set

 

 

 

 

motor temperature threshold (p0604).

 

 

Note:

 

 

 

 

When the motor temperature threshold is exceeded, only an alarm is output initially to warn you of this. The

 

alarm is canceled automatically when the temperature no longer exceeds the alarm threshold.

 

 

If the overtemperature is present for longer than the value set via p0606, a fault is output to warn you of this.

 

Motor temperature monitoring can be switched-out via p0600 = 0.

 

 

Application:

 

 

 

 

The user can respond to this message by reducing the load. thereby preventing the motor from shutting down with

 

the "Motor temperature exceeded" fault after the set time has elapsed.

 

7

No thermal overload in power

1

No thermal overload in power unit alarm

BO: r2135.15

 

section alarm

 

The temperature of the heat sink in the power

(inverted)

 

 

 

section is within the permissible range.

 

 

 

0

Thermal overload in power unit alarm

 

 

 

 

The temperature of the heat sink in the power unit is

 

 

 

 

outside the permissible range.

 

 

 

 

If the overtemperature remains, the drive switches

 

 

 

 

itself off after approx. 20 s.

 

8

Speed setp - act val deviation in

1

The speed setpoint/actual value is within the

BO: r2199.4

 

tolerance t_on

 

tolerance p2163: The signal is switched on after the

 

 

 

 

delay specified in p2167 has elapsed.

 

 

 

0

The speed setpoint/actual value is outside the

 

 

 

 

tolerance.

 

9...

Reserved

1

-

-

12

 

0

-

 

 

 

 

13

Pulses enabled

1

Pulses enabled

BO: r0899.11

 

 

 

The pulses for activating the motor are enabled.

 

 

 

0

Pulses inhibited

 

 

Application:

 

 

 

 

Armature short-circuit protection must only be switched on when the pulses are inhibited.

 

 

This signal can be evaluated as one of many conditions when armature short-circuit protection is activated.

14

Reserved

1

-

-

15

 

0

-

 

Drive Functions

371

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4