Basic information about the drive system 12.7 Examples of replacing components

Action

Reaction

Comments

Load the project from the

Alarm disappears

The new order number is stored

Control Unit to the

 

in the RAM of the Control Unit

STARTER (PG)

 

and has to be copied to the non-

Configure the replacement

 

volatile memory with p0971 or

drive and select the current

 

p0977.

component

 

 

Load the project to the

 

 

Control Unit (target system)

 

 

The component has been successfully replaced

Example: (p9909 = 1) Replacing a defective component with an identical order number Precondition:

The replaced component has an identical order number

The serial number of the new replacement component must not be contained in the stored target topology of the Control Unit.

Topology comparison component replacement active p9909 = 1.

Sequence:

During startup of the Control Unit, the serial number of the new component is automatically transferred to the target topology and saved.

Example: (p9909 = 0) Replacing a defective component with an identical order number Precondition:

The replaced component has an identical order number

Topology comparison component replacement inactive p9909 = 0.

Table 12-12 Example: Replacing a Motor Module

Action

Reaction

Comments

Switch off the power supply

Replace the defective component and connect the new one

Switch on the power supply

Alarm A01425

500

Drive Functions

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4