Communication PROFIBUS DP/PROFINET IO 10.1 Communications according to PROFIdrive

Table 10-7 Description of E_CTW1 (control word for INFEED)

Bit

Meaning

 

Comments

BICO

0

ON/OFF1

0/1

ON

BI: p0840

 

 

 

Pulse enable possible

 

 

 

0

OFF1

 

 

 

 

Reduce DC link voltage via ramp (p3566), pulse

 

 

 

 

inhibit/line contactor open

 

1

OFF2

1

No OFF2

BI: p0844

 

 

 

Enable possible

 

 

 

0

OFF2

 

 

 

 

Immediate pulse cancellation and power-on

 

 

 

 

inhibit

 

 

Note:

 

 

 

 

 

Control signal OFF2 is generated by ANDing BI: p0844 and BI: p0845.

 

2

Reserved

-

-

 

-

3

Enable operation

1

Enable operation

BI: p0852

 

 

 

Pulse enable is present

 

 

 

0

Disable operation

 

 

 

 

Pulse inhibit is present

 

4

Reserved

-

-

 

-

5

Inhibit motor operation

1

Inhibit motor operation

BI: p3532

 

 

 

Motoring operation as step-up converter is

 

 

 

 

inhibited.

 

 

 

0

Enable motor operation

 

 

 

 

Motoring operation as step-up converter is

 

 

 

 

enabled.

 

 

Note:

 

 

 

 

 

When "Inhibit motoring operation" is present, power can still be drawn from the DC link. The DC link voltage is then

 

no longer controlled. The voltage level is the same as the rectified value of the current line voltage.

 

6

Inhibit regenerating

1

Inhibit regenerative operation

BI: p3533

 

 

 

Regenerative operation is inhibited.

 

 

 

0

Enable regenerative operation

 

 

 

 

Regenerative operation is enabled.

 

 

Note:

 

 

 

 

 

If regenerative operation is inhibited and power is fed to the DC link (e.g. by braking the motor), the DC link voltage

 

increases (F30002).

 

 

 

 

7

Acknowledge error

0/1

Acknowledge error

 

BI: p2103

 

Note:

 

 

 

 

 

Faults are acknowledged at a 0/1 edge via BI: p2103 or BI: p2104 or BI: p2105.

 

8

Reserved

-

-

 

-

9

Reserved

-

-

 

-

10

Master ctrl by PLC

1

Control via PLC

BI: p0854

 

 

 

This signal must be set so that the process data

 

 

 

 

transferred via PROFIdrive is accepted and

 

 

 

 

becomes effective.

 

 

 

0

No control via PLC

 

 

 

 

Process data transferred via PROFIdrive is

 

 

 

 

rejected - i.e. it is assumed to be zero.

 

Drive Functions

359

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Page 359