11.2Switching on a drive object x_Infeed by means of a vector drive object

With the setting p8839(x) = 2 and the COMM board missing / defective, the respective interface is not automatically fed by the onboard interface. Instead, an alarm is issued.

Alarm

A_8550

PZD interface hardware assignment incorrect

Description:

The assignment of the hardware to the PZD interface has been incorrectly parameterized.

Values:

1: Only one of the two indexes is not equal to 99

2:Both PZD interfaces have been assigned the same hardware

3:Assigned COMM board missing

4:CBC10 has been assigned to interface 1

11.2Switching on a drive object x_Infeed by means of a vector drive object

Description

'2;,QIHHG

'29HFWRU

 

 

,QIHHGRSHUDWLRQ

,QIHHG

 

 

 

 

 

%,$FNQRZOHGJHIDXOW

U

S

6HWDFNQRZOHGJH

 

 

S>&@

 

,QIHHGIDXOW

%,,QIHHGIDXOW

FRPPDQG



 

S

U

 

U

 

%,$XWRPDWLFUHVWDUW

 

$XWRPDWLFUHVWDUW

 

 

S

 

 

%,,QIHHGSRZHU

U

 

 

,QIHHGSRZHUIDLOXUH

S

 

(QHUJL]HOLQHFRQWDFWRU

 

 

U

 

%,212))

 

U

(QHUJL]HOLQHFRQWDFWRU

 

S>&@

 

 

 

 

 

 

 

 

U

 

 

 

 

/LQH

 

 

 

FRQWDFWRU

 

 

Figure 11-1 BICO interconnection

Using this BICO interconnection, a drive object (DO) x_Infeed can be switched-in by a vector drive object. This power-on version is mainly used for chassis units, if only one Line Module and one Motor Module are used. If the associated application requires an automatic restart function then the following procedure is recommended in order to implement it:

The automatic restart function is activated on the DO vector (p1210).

In addition to the automatic restart function, the flying restart function (p1200) must be activated on DO vector if it must be assumed that an automatic restart must be made for a motor that is still rotating.

454

Drive Functions

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Page 454