Function modules 7.9 Basic positioner

Instructions for switching data sets

Using drive data set switching (DDS), motor data sets (p0186) and encoder data sets (p0187 to p0189) can be switched. The following table shows when the reference bit (r2684.11) or the status of the adjustment with absolute encoders (p2507) is reset.

In the following cases, when a DDS switch takes place, the current actual position value becomes invalid (p2521 = 0) and the reference point (r2684.11 = 0) is reset.

The EDS that is effective for the position control changes.

The encoder assignment changes (p2502).

The mechanical relationships change (p2503...p2506)

With absolute encoders, the status of the adjustment (p2507) is also reset, if the same absolute encoder is selected for the position control although the mechanical relationships have changed (p2503 ... p2506).

In operating mode, an error message (F07494) is also generated.

The following table contains a few examples for data set switching. The initial data set is always DDS0.

Table 7-5

DDS switch without load gearbox position tracking

 

 

 

 

 

 

 

 

 

 

 

 

 

DDS

p186

 

p187

p188

p189

Encoder

Mecha-

Load

Changeover response

 

(MDS)

(encoder_1)

(encoder_2)

(encoder_3)

for

nical

gearbox

 

 

 

 

 

 

 

position

conditions

position

 

 

 

 

 

 

 

control

p2504/

tracking

 

 

 

 

 

 

 

p2502

p2505/

 

 

 

 

 

 

 

 

 

p2506 or

 

 

 

 

 

 

 

 

 

p2503

 

 

0

0

 

EDS0

EDS1

EDS2

encoder_1

xxx

disabled

---

1

0

 

EDS0

EDS1

EDS2

encoder_1

xxx

disabled

Switching during pulse

 

 

 

 

 

 

 

 

 

inhibition or operation has

 

 

 

 

 

 

 

 

 

no effect

2

0

 

EDS0

EDS1

EDS2

encoder_1

yyy

disabled

Pulse disabling: Position

 

 

 

 

 

 

 

 

 

actual value preprocessing

 

 

 

 

 

 

 

 

 

is newly initiated 1) and

 

 

 

 

 

 

 

 

 

reference bit 2) is reset.

 

 

 

 

 

 

 

 

 

Operation:

 

 

 

 

 

 

 

 

 

Error message is

 

 

 

 

 

 

 

 

 

generated. Position actual

 

 

 

 

 

 

 

 

 

value preprocessing is

 

 

 

 

 

 

 

 

 

newly initiated 1) and

 

 

 

 

 

 

 

 

 

reference bit 2) is reset.

3

0

 

EDS0

EDS1

EDS2

encoder_2

xxx

disabled

Pulse disabling: Position

4

0

 

EDS0

EDS3

EDS2

encoder_2

xxx

disabled

actual value preprocessing

 

is newly initiated 1) and

5

1

 

EDS4

EDS1

EDS2

encoder_1

xxx

disabled

 

 

266

Drive Functions

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Page 266
Image 266
Efficient Networks S120 manual Instructions for switching data sets