Efficient Networks S120 manual CTW2 control word, ECTW1 control word for Infeed

Models: S120

1 560
Download 560 pages 21.93 Kb
Page 358
Image 358

Communication PROFIBUS DP/PROFINET IO 10.1 Communications according to PROFIdrive

Bit

Meaning

 

Comments

BICO

12

Reserved

-

-

-

13

External block change

0/1

External set change is initiated

BI: 2632

 

 

0

No effect

 

14

Reserved

-

-

-

15

Reserved

-

-

-

CTW2 (control word 2)

See function diagram [2444]

Table 10-6 Description of CTW2 (control word 2)

Bit

Meaning

 

Comments

BICO

0

Drive data set selection DDS bit 0

-

Drive data set selection

BI: p0820[0]

1

Drive data set selection DDS bit 1

-

(5 bit counter)

BI: p0821[0]

 

2

Drive data set selection DDS bit 2

-

 

BI: p0822[0]

3

Drive data set selection DDS bit 3

-

 

BI: p0823[0]

4

Drive data set selection DDS bit 4

-

 

BI: p0824[0]

5...6

Reserved

-

-

-

7

Parking axis

1

Request parking axis (handshake with ZSW2 bit

BI: p0897

 

 

 

7)

 

 

 

0

No request

 

8

Travel to fixed endstop

1

Select "Travel to fixed stop"

BI: p1545

 

 

 

The signal must be set before the fixed stop is

 

 

 

 

reached.

 

 

 

1/0

Deselect "Travel to fixed stop"

 

 

 

 

The signal must be set before the fixed stop is

 

 

 

 

reached

 

9

Reserved

-

-

-

10

Reserved

-

-

-

11

Motor switchover

0/1

Motor switchover complete

BI: p0828[0]

 

 

0

No effect

 

12

Drive unit sign-of-life bit 0

-

User data integrity (4-bit counter)

CI: p2045

13

Drive unit sign-of-life bit 1

-

 

 

14

Drive unit sign-of-life bit 2

-

 

 

15

Drive unit sign-of-life bit 3

-

 

 

E_CTW1 (control word for INFEED)

See function diagram [8920]

358

Drive Functions