Communication PROFIBUS DP/PROFINET IO 10.1 Communications according to PROFIdrive

Field

Data type

Values

Comment

 

The format and number specify the adjoining space containing values in the telegram.

 

Data types in conformity with PROFIdrive Profile shall be preferred for write access. Bytes,

 

words and double words are also possible as a substitute.

No. of values

Unsigned8

0x00 ... 0xEA

No. 0 ... 234

 

 

 

Limited by DPV1 telegram length

 

Specifies the number of subsequent values.

 

Error values

Unsigned16

 

 

 

 

0x0000 ... 0x00FF

Meaning of error value

 

 

 

--> see table 4-29

 

The error values in the event of a negative response.

 

 

If the values make up an odd number of bytes, a zero byte is appended. This ensures the

 

integrity of the word structure of the telegram.

 

Values

Unsigned16

 

 

 

 

0x0000 ... 0x00FF

 

 

The values of the parameter for read or write access.

 

 

If the values make up an odd number of bytes, a zero byte is appended. This ensures the

 

integrity of the word structure of the telegram.

 

Error values in DPV1 parameter responses

Table 10-27 Error values in DPV1 parameter responses

Error

Meaning

Comment

Additional

value

 

 

info

0x00

Illegal parameter number

Access to a parameter which does not exist.

0x01

Parameter value cannot be changed

Modification access to a parameter value which cannot be

Subindex

 

 

changed.

 

0x02

Lower or upper value limit exceeded

Modification access with value outside value limits.

Subindex

0x03

Invalid subindex

Access to a subindex which does not exist.

Subindex

0x04

No array

Access with subindex to an unindexed parameter.

0x05

Wrong data type

Modification access with a value which does not match the

 

 

data type of the parameter.

 

0x06

Illegal set operation (only reset

Modification access with a value not equal to 0 in a case

Subindex

 

allowed)

where this is not allowed.

 

0x07

Description element cannot be

Modification access to a description element which cannot

Subindex

 

changed

be changed.

 

0x09

No description data

Access to a description which does not exist (the

 

 

parameter value exists).

 

0x0B

No operating priority

Modification access with no operating priority.

0x0F

No text array exists

Access to a text array which does not exist (the parameter

 

 

value exists).

 

0x11

Request cannot be executed due to

Access is not possible temporarily for unspecified reasons.

 

operating status

 

 

0x14

Illegal value

Modification access with a value which is within the limits

Subindex

 

 

but which is illegal for other permanent reasons

 

 

 

(parameter with defined individual values).

 