Efficient Networks S120 manual Overview of key parameters see Sinamics S List Manual

Models: S120

1 560
Download 560 pages 21.93 Kb
Page 55
Image 55

Extended setpoint channel 2.5 Motorized potentiometer

Setting value (p1043/p1044)

Initial rounding-off active/not active (p1030.2)

Non-volatile storage of the setpoints via p1030.3

Configurable setpoint for Power On (p1030.0)

Starting value is the value in p1040 (p1030.0 = 0)

Starting value is the stored value (p1030.0 = 1)

Function diagrams (see SINAMICS S List Manual)

1550 Setpoint channel

2501 Control word sequential control

3020 Motorized potentiometer

Overview of key parameters (see SINAMICS S List Manual)

p1030[DDS] Motorized potentiometer, configuration

p1035[CDS] BI: Motorized potentiometer, setpoint, raise

p1036[CDS] BI: Motorized potentiometer, lower setpoint

p1037[DDS] Motorized potentiometer, maximum speed

p1038[DDS] Motorized potentiometer, minimum speed

p1039[CDS] BI: Motorized potentiometer, inversion

p1040[DDS] Motorized potentiometer, starting value

p1041[CDS] BI: Motorized potentiometer, manual/automatic

p1042[CDS] CI: Motorized potentiometer, automatic setpoint

p1043[CDS] BI: Motorized potentiometer, accept setpoint

p1044[CDS] CI: Motorized potentiometer, setting value

r1045 CO: Motorized potentiometer, speed setpoint in front of the ramp function generator

p1047[DDS]Motorized potentiometer, ramp-up time

p1048[DDS] Motorized potentiometer, ramp-down time

r1050 CO: Motorized potentiometer, setpoint after the ramp function generator

p1082[DDS] Maximum speed

Parameterization with STARTER

In the STARTER commissioning tool, the "Motorized potentiometer" parameter screen in the project navigator under the relevant drive is activated by double-clicking Setpoint channel -> Motorized potentiometer.

Drive Functions

55

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Page 55