Communication PROFIBUS DP/PROFINET IO 10.1 Communications according to PROFIdrive

Properties

No additional parameters need to be entered in addition to the bus configuration in order to activate this function, the master and slave must only be preset for this function (PROFIBUS).

The master-side default setting is made via the hardware configuration, e.g. B. HW Config with SIMATIC S7. The slave-side default setting is made via the parameterization telegram when the bus is ramping up.

Fixed sampling times are used for all data communication.

The Global Control (GC) clock information on PROFIBUS is transmitted before the beginning of each cycle.

The length of the clock cycle depends on the bus configuration. When the clock cycle is selected, the bus configuration tool (e.g. HW Config) supports:

High number of drives per slave/drive unit -> long cycle

High number of slaves/drive units -> long cycle

A sign-of-life counter is used to monitor user data transfer and clock pulse failures.

Overview of closed-loop control

Sensing of the actual position value on the slave can be performed using:

Indirect measuring system (motor encoder)

Additional direct measuring system

The encoder interface must be configured in the process data.

The control loop is closed via the PROFIBUS.

The position controller is located on the master.

The current and speed control systems and actual value sensing (encoder interface) are located on the slave.

The position controller clock cycle is transmitted across the field bus to the slaves.

The slaves synchronize their speed and/or current controller cycle with the position controller cycle on the master.

The speed setpoint is specified by the master.

390

Drive Functions

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Page 390
Image 390
Efficient Networks S120 manual Properties, Overview of closed-loop control