Vector control 4.7 Torque control

OFF2

Immediate pulse suppression, the drive coasts to standstill.

The motor brake (if parameterized) is closed immediately.

Power-on disable is activated.

OFF3

Switch to speed-controlled operation

n_set = 0 is input immediately to brake the drive along the OFF3 deceleration ramp (p1135).

When zero speed is detected, the motor brake (if parameterized) is closed.

The pulses are suppressed when the motor brake application time (p1217) has elapsed. Standstill is detected when the actual speed value is less than the speed threshold (p1226) or when the monitoring time (p1227) that started when speed setpoint ≤ speed threshold (p1226) has expired.

Power-on disable is activated.

Function diagrams (see SINAMICS S List Manual)

● 6060 Torque setpoint

Overview of key parameters (see SINAMICS S List Manual)

p0341 motor moment of inertia

p0342 Ratio between the total moment of inertia and that of the motor

p1300 Open-loop/closed-loop control operating mode

p1499 Accelerating for torque control, scaling

p1501 BI: Change over between closed-loop speed/torque control

p1503 CI: Torque setpoint

p1511 CI: Supplementary torque 1

p1512 CI: Supplementary torque 1 scaling

p1513 CI: Supplementary torque 2

p1514 Supplementary torque 2 scaling

r1515 Supplementary torque total