Servo control

 

 

 

 

 

3.5 Torque setpoint limitation

 

Fixed and variable torque limit settings

 

 

 

 

Table 3-1

Fixed and variable torque limit settings

 

 

 

 

 

 

 

 

 

 

 

 

Selection

 

Torque limitation mode

 

 

Mode

 

Maximum upper or lower torque limits

Maximum motor or regenerative mode torque

 

 

 

p1400.4 = 0

 

limits p1400.4 = 1

 

 

Fixed torque limit

Upper torque limit (as positive

p1520

Motor mode torque limit (as

p1520

 

 

 

value)

 

positive value)

 

 

 

 

Lower torque limit (as negative

p1521

Regenerative mode torque limit (as

p1521

 

 

 

value)

 

negative value)

 

 

Source for variable torque

Upper torque limit

p1522

Motor mode torque limit

p1522

 

limit

 

Lower torque limit

p1523

Regenerative mode torque limit

p1523

 

 

 

 

Source for variable scaling

Upper torque limit

p1528

Motor mode torque limit

p1528

 

factor of torque limit

Lower torque limit

p1529

Regenerative mode torque limit

p1529

 

 

 

 

Torque offset for torque

Shifts the upper and lower

p1532

Shifts the motor and regenerative

p1532

 

limit

 

torque limits together

 

mode torque limits together

 

Variants of torque limitation

The following variants are available:

1.No settings entered:

The application does not require any additional restrictions to the torque limits.

2.Fixed limits are required for the torque:

The fixed upper and lower limits or alternatively the fixed motor and regenerative limits can be specified separately by different sources.

3.Dynamic limits are required for the torque:

The dynamic upper and lower limit or, alternatively, the dynamic motor and regenerative limit can be specified separately by different sources.

Parameters are used to select the source of the current limit.

4.A torque offset can be parameterized.

5.In addition, the power limits can be parameterized separately for motor and regenerative mode.

NOTICE

Negative values at r1534 or positive values at r1535 represent a minimum torque for the other torque directions and can cause the drives to rotate if no load torque is generated to counteract this (see function diagram 5630 in the SINAMICS S List Manual).

Drive Functions

73

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Page 73
Image 73
Efficient Networks S120 manual Fixed and variable torque limit settings, Variants of torque limitation, Servo control