Infeed

1.3 Basic Infeed

If a braking resistor has not been connected for 20 kW and 40 kW Basic Line Modules Booksize, the braking chopper must be deactivated via p3680 = 1.

Function diagrams (see SINAMICS S List Manual)

8720 Control word sequential control infeed

...

8760 Messages and monitoring functions

Overview of key parameters (see SINAMICS S List Manual)

r0002 Infeed/operating display

r0046 CO/BO: Infeed missing enable signals

p0210 Device supply voltage

p0840 BI: ON/OFF1

p0844 BI: 1. OFF2

r0898 CO/BO: Control word sequential control infeed

r0899 CO/BO: Status word sequence control infeed

r2138 CO/BO: Control word, faults/alarms

r2139 CO/BO: Status word, faults/alarms 1

p3680 Inhibit braking chopper

1.3.2Basic Infeed open-loop control

Description

The Basic Line Module can be controlled via the BICO interconnection by means of terminals or the field bus. The operating status is indicated on the operating display r0002. The missing enable signals for operation (r0002 = 00) are mapped in parameter r0046. The EP terminals (enable pulses) must be connected in accordance with the Equipment Manual.

Acknowledge error

Errors that are still present but the causes of which have been rectified can be acknowledged by means of a 0/1 edge at the "Acknowledge error" (p2103) signal.

40

Drive Functions

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4