Jog properties

If both jog signals are issued at the same time, the current speed is maintained (constant velocity phase).

Jog setpoints are approached and exited via the ramp-function generator.

The jog function can be activated from the "ready to start" status and from the OFF1 deceleration ramp.

If ON/OFF1 = "1" and jog are selected simultaneously, ON/OFF1 has priority.

OFF2 and OFF3 have priority over jogging.

In jog mode, the main speed setpoints (r1078) and the supplementary setpoints 1 and 2 (p1155 and p1160) are inhibited.

The suppression bandwidths (p1091 ... p1094) and the minimum limit (p1080) in the setpoint channel are also active in jog mode.

In jog mode, ZSWA.02 (operation enabled) is set to "0" because the speed setpoint has not been enabled for control.

The ramp-function generator cannot be frozen (via p1141) in jog mode (r0046.31 = 1).