Communication PROFIBUS DP/PROFINET IO 10.2 Communication via PROFIBUS DP

Name

Value1)

Limit value

Description

TO

4

TDX + TO_MIN

Time of setpoint transfer

 

 

≤ TO ≤ TDP

This is the time at which the transferred setpoints (speed

 

 

 

setpoint) are accepted by the closed-loop control system after

 

 

 

the start of the cycle.

 

 

 

TO = integer multiple of TBASE_IO

 

 

 

Servo calculation: TO = 4 ∙ TBASE_IO = 500 µs

 

 

 

When TO = 0: TO ≐ TDP

 

 

 

Vector calculation: TO = 4 ∙ 1000 µs = 4000 µs

 

 

 

When TO = 0: TO ≐ TDP

 

 

 

TO corresponds to the largest speed controller cycle (p0115[1])

 

 

 

of a drive object (vector) in the drive unit.

 

 

TO_MIN = 1

Servo:

 

 

 

Minimum time distance between TO and TDX

 

 

 

TO_MIN = 1 ∙ TBASE_IO = 125 µs

 

 

 

Vector:

 

 

 

Minimum time distance between TO and TDX

 

 

 

TO_MIN = 1 ∙ Tn_reg = 1000 µs

 

 

 

Tn_reg corresponds to the largest speed controller cycle

 

 

 

(p0115[1]) of a drive object (vector) in the drive unit.

TDX

E10 hex

TDX < TDP

Data exchange time

 

 

This is the time required within one cycle for transferring

 

3600 dec

 

process data to all available slaves.

 

 

 

TDX = integer multiple of TBit

 

 

 

TBit = 1/12 µs at 12 MBaud

 

 

 

calculation: TDX = 3600 • TBIT = 300 µs

TPLL_W

0

-

PLL window

 

 

 

(half the width of the GC synchronization window)

 

 

 

The following applies to the setting:

 

 

 

Small window --> minimization of synchronization

 

 

 

fluctuations on the drive

 

 

 

Large window --> higher tolerance of GC fluctuations

 

 

 

Calculation (assumption: TPLL_W = A hex ≐ 10 dez)

 

 

 

TPLL_W = 10 • TBIT = 0.833 µs

 

 

 

TBit = 1/12 µs at 12 Mbps

TPLL_D

0

-

PLL dead time

 

 

 

The PLL dead time can be used to compensate for different

 

 

 

data transfer times to the slaves (e.g. due to repeaters).

 

 

 

The slaves with faster transfer times are delayed by a

 

 

 

corresponding PLL dead time.

 

 

 

Calculation: TPLL_D = 0 ∙ TBIT = 0 µs

 

 

 

TBit = 1/12 µs at 12 MBaud

GC

 

 

Global Control Telegram (Broadcast Telegram)

TTH

 

 

Token hold time

 

 

 

This time is calculated by the engineering system.

Dx

 

 

Data_Exchange

 

 

 

This service is used to implement user data exchange between

 

 

 

master and slave 1 - n.

418

Drive Functions

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Page 418