Basic information about the drive system

12.10Rules for wiring with DRIVE-CLiQ

Also change the current controller sampling time and the sampling time of the inputs/outputs of the DOs not involved so that they again fit into the time grid.

Note

You can call up the "Topology" screen in STARTER to change and/or check the DRIVE-CLiQ topology for each drive unit.

Note

To enable the function "Automatic configuration" to assign the encoders to the drive, the recommended rules below must be observed.

Recommended rules

The DRIVE-CLiQ cable from the Control Unit must be connected to X200 on the first booksize power section or X400 on the first chassis power section.

The DRIVE-CLiQ connections between the power sections must each be connected from interface X201 to X200/from X401 to X400 on the follow-on component.

A Power Module with the CUA31 should be connected to the end of the DRIVE-CLiQ line.

&8



;

;

;

;

6LQJOH

0RWRU

0RGXOH

;;

;;

;;

'RXEOH

0RWRU

0RGXOH

;

;

;

;

6LQJOH

0RWRU

0RGXOH

;;

;;

;;

3RZHU0RGXOH

%ORFNVL]H

&8$

;

;

;

Figure 12-23 Example: DRIVE-CLiQ line

● The motor encoder must be connected to the associated power unit.

Table 12-14 Connecting the motor encoder via DRIVE-CLiQ

Component

Connecting the motor encoder via DRIVE-CLiQ

Single Motor Module Booksize

X202

Double Motor Module (booksize)

Motor connection X1: Encoder at X202

 

Motor connection X2: Encoder at X203

Single Motor Module Chassis

X402

Power Module Blocksize

CUA31: Encoder at X202

 

CU310: Encoder at X100 or via TM31 at X501

Power Module Chassis

X402

508

Drive Functions

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Page 508