Servo control 3.12 Motor data identification

Table 3-11 Data determined using p1910 for induction motors (stationary measurement)

Determined data (gamma)

Data that are accepted (p1910 = 1)

r1912 identified stator resistance

p0350 motor stator resistance, cold

 

+ p0352 cable resistance

r1913 rotor time constant identified

r0384

 

motor rotor time constant/damping time constant, d axis

r1915 stator inductance identified

-

r1925 threshold voltage identified

-

r1927 rotor resistance identified

r0374 motor resistance cold (gamma)

 

p0354

r1932 d inductance

r0377 motor leakage inductance, total (gamma)

 

p0353 motor series inductance

 

p0356 motor leakage inductance

 

p0358 motor leakage inductance

 

p1715 current controller P gain

 

p1717 current controller integral action time

r1934 q inductance identified

-

r1936 magnetizing inductance identified

r0382 motor main inductance, transformed (gamma)

 

p0360 motor main inductance

 

p1590 flux controller P gain

 

p1592 flux controller integral action time

r1973 encoder pulse number identified

-

Note:

The encoder pulse number is only determined with a very high degree of inaccuracy (p0407/p0408) and is only suitable for making rough checks. The sign is negative if inversion is required (p0410.0).

-

p0410 encoder inversion actual value

Note:

If the encoder inversion is changed using MotID, fault F07993 is output, which refers to a possible change in the direction of rotation and can only be acknowledged by p1910 = -2.

Table 3-12 Data determined using p1960 for induction motors (rotating measurement)

Determined data (gamma)

Data that are accepted (p1960 = 1)

r1934 q inductance identified

-

r1935 q inductance identification current

 

Note:

The q inductance characteristic can be used as basis to manually determine the data for the current controller adaptation (p0391, p0392 and p0393).

r1936 magnetizing inductance identified

r0382 motor main inductance, transformed (gamma)

 

p0360 motor main inductance

 

p1590 flux controller P gain

 

p1592 flux controller integral action time

r1948 magnetizing current identified

p0320 rated motor magnetizing current

r1962 saturation characteristic magnetizing current

-

identified

 

r1963 saturation characteristic stator inductance

-

identified

 

Drive Functions

95

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4