Basic information about the drive system 12.10 Rules for wiring with DRIVE-CLiQ

Rules for FW2.5 SP1:

The Voltage Sensing Module (VSM) must be connected to a dedicated DRIVE-CLiQ port of the Control Unit.

If possible, the CUA31 should be connected at the end of the line.

Restrictions for Safety Extended Functions:

Maximum of 5 servo axes with Extended Functions for standard settings of cycle times (monitoring cycle: 12 ms; application cycle: 125 µs).

Maximum of 2 vector axes with Extended Functions for standard settings of cycle times (monitoring cycle: 12 ms; application cycle: 250 µs).

TM54F must not be connected in line with the Motor Modules.

A maximum of 4 Motor Modules with Extended Functions in line.

Table 12-20 Maximum number of drives that can be controlled by a Control Unit 320

 

Servo

Vector V/f (=vector

 

 

without speed control

 

 

function module and

 

 

without encoder)

Number of

1 Active Line Module +

1

Active Line Module +

components

6 Motor Modules1)

4

Motor Modules1)

 

 

(sampling time of current

 

 

controller 250 µs / speed

 

 

controller 1000 µs)

 

 

1

Active Line Module +

 

 

6

Motor Modules1)

 

 

(sampling time of current

 

 

controller 400 µs / speed

 

 

controller 1600 µs)

 

 

1

Active Line Module +

 

 

8

Motor Modules1)

 

 

(sampling time of current

 

 

controller 500 µs / speed

 

 

controller 4000 µs)

 

Servo and vector V/f:

 

 

 

1 Active Line Module + 5 Motor Modules 1)

 

(servo: Current controller 125 µs / speed controller

125µs

Vector V/f:

sampling time of current controller 250 µs / speed controller 1000 µs

with max. 2 V/f drives

sampling time of current controller 400 µs / speed controller 1600 µs with more than 2 V/f drives)

Vector

1 Active Line Module +

2Motor Modules1) (sampling time of current controller 250 µs / speed controller 1000 µs)

1 Active Line Module +

4Motor Modules1) (sampling time of current controller 400 µs / speed controller 1600 µs)

Notes on the maximum number of drives that can be controlled by a CU320:

In addition, the "Safe Standstill" function can be activated and a TM31 connected.

No function modules must be activated.

1)If a CUA31 is connected as the first module to the Control Unit, then the maximum number is decreased by one.

Drive Functions

513

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4