Infeed

1.2 Smart Infeed

1.2.3Smart Infeed open-loop control

Description

The Smart Line Module can be controlled via the BICO interconnection by means of terminals or the field bus. The operating status is indicated on the operating display r0002. The missing enable signals for operation (r0002 = 00) are mapped in parameter r0046. The EP terminals (enable pulses) must be connected in accordance with the Equipment Manual. The drive unit must have been commissioned for the first time.

Acknowledge error

Errors that are still present but the causes of which have been rectified can be acknowledged by means of a 0/1 edge at the "Acknowledge error" (p2103) signal.

Drive Functions

35

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Page 35
Image 35
Efficient Networks S120 manual Smart Infeed open-loop control, Description