Efficient Networks S120 manual Vdc control, Angular commutation offset commissioning support p1990

Models: S120

1 560
Download 560 pages 21.93 Kb
Page 102
Image 102

Servo control 3.14 Vdc control

Angular commutation offset commissioning support (p1990)

The function for determining the commutation angle offset is activated via p1990=1. The commutation angle offset is entered in p0431. This function can be used in the following cases:

Single calibration of the pole position for encoders with absolute information (exception: The Hall sensor must always be mechanically adjusted.)

Calibrating the zero mark position for fine synchronization

Table 3-15 Mode of operation of p0431

 

Incremental without

Incremental with one

Incremental with distance-

EnDat absolute

 

zero mark

zero mark

coded zero marks

encoder

C/D track

p0431

p0431

Currently not available

Not permitted

 

shifts the commutation

shifts the commutation

 

 

 

with respect to the C/D

with respect to the C/D

 

 

 

track

track and zero mark

 

 

Hall sensor

p0431

p0431

p0431

Not permitted

 

does not influence the

does not influence the

does not influence the Hall

 

 

Hall sensor. The Hall

Hall sensor.

sensor.

 

 

sensor must be

p0431

p0431

 

 

mechanically adjusted.

shifts the commutation

shifts the commutation with

 

 

 

with respect to the zero

respect to the absolute

 

 

 

mark

position (after two zero marks

 

 

 

 

have been passed)

 

Pole position

p0431

p0431

p0431

p0431

identification

no effect

shifts the commutation

shifts the commutation with

shifts the commutation

 

 

with respect to the zero

respect to the absolute

with respect to the

 

 

mark

position (after two zero marks

EnDat absolute

 

 

 

have been passed)

position

Note

When fault F07414 occurs, p1990 is automatically started; if p1980 is not equal to 99 and p0301 does not refer to a catalog motor with an encoder that is adjusted in the factory.

3.14Vdc control

Description

Vdc control can be activated if overvoltage or undervoltage is present in the DC link line-up. In the line-up, one or more drives can be used to relieve the DC link. This prevents a fault from occurring due to the DC link voltage and ensures that the drives are always ready to use

This function is activated by means of the configuration parameter (p1240). It can be activated if an overvoltage or undervoltage is present. The torque limits of the motors at which the Vdc controller is active can be affected if discrepancies in the DC link voltage are

102

Drive Functions

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Page 102
Image 102
Efficient Networks S120 manual Vdc control, Angular commutation offset commissioning support p1990