Servo control

3.12 Motor data identification

Table 3-9

Type plate data

 

 

 

 

 

 

 

 

 

Induction motor

 

Permanent-magnet synchronous motor

p0304 rated voltage

p0304 rated voltage

p0305 rated current

p0305 rated current

p0307 rated power

p0307 rated power (alternative p0316)

p0308 rated power factor (cos ϕ)

p0311 rated speed

p0310 rated frequency

p0314 motor pole pair number

p0311 rated speed

 

or p0315 motor pole pair width

p0322 maximum motor speed

p0322 maximum motor speed

p0353 motor series inductance

p0323 maximum motor current

p0400ff encoder data

p0353 motor series inductance

 

 

 

p0400ff encoder data

Since the type plate data contains the initialization values for identification, you must ensure that it is entered correctly and consistently to enable the above data to be determined.

Parameters to control the MotID

The following parameters influence the MotID:

Table 3-10 Parameters for control

Static measurement (motor data identification)

 

 

rotating measurement

p0640 current limit

p0640 current limit

p1215

Motor holding brake configuration

p1082

Maximum speed

p1909

Motor data identification control word

p1958 motor data identification ramp-up/ramp-down time

p1910

Motor data identification, stationary

p1959

Rotating measurement configuration

p1959.14/.15 clockwise/counter-clockwise direction or

p1960

Rotating measurement selection

rotation permitted

 

 

 

Note:

If a brake is being used and is operational (p1215 = 1, 3), then the stationary measurement with closed brake is carried- out. If possible (e.g. no hanging/suspended axis), we recommend that the brake is opened before the MotID (p1215 = 2). This also means that the encoder size can be adjusted and the angular commutation calibrated.

3.12.1Motor data identification - induction motor

Induction motor

The data are identified in the gamma equivalent circuit diagram and displayed in r19xx. The motor parameters p0350, p0354, p0356, p0358 and p0360 taken from the MotID refer to the T equivalent circuit diagram of the induction machine and cannot be directly compared. This is the reason that an r parameter is listed in the table, which displays the parameterized motor parameters in the gamma equivalent circuit diagram.

94

Drive Functions

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Page 94
Image 94