Communication PROFIBUS DP/PROFINET IO 10.1 Communications according to PROFIdrive

Error

Meaning

Comment

Additional

value

 

 

info

0x15

Response too long

The length of the present response exceeds the maximum

 

 

transfer length.

 

0x16

Illegal parameter address

Impermissible or unsupported value for attribute, number

 

 

of elements, parameter number, subindex or a

 

 

 

combination of these.

 

0x17

Illegal format

Write request: illegal or unsupported parameter data

 

 

format

 

0x18

No. of values inconsistent

Write request: a mismatch exists between the number of

 

 

values in the parameter data and the number of elements

 

 

 

in the parameter address.

 

0x19

Drive object does not exist

You have attempted to access a drive object that does not

 

 

exist.

 

0x65

Presently deactivated.

You have tried to access a parameter that, although

 

 

available, is currently inactive (e.g. n control set and

 

 

 

access to parameter from V/f control).

 

0x6B

Parameter %s [%s]: no write access

 

for the enabled controller

 

 

0x6C

Parameter %s [%s]: unit unknown

0x6D

Parameter %s [%s]: Write access

 

only in the commissioning state,

 

 

 

encoder (p0010 = 4).

 

 

0x6E

Parameter %s [%s]: Write access

 

only in the commissioning state,

 

 

 

motor (p0010 = 3).

 

 

0x6F

Parameter %s [%s]: Write access

 

only in the commissioning state,

 

 

 

power unit (p0010 = 2).

 

 

0x70

Parameter %s [%s]: Write access

 

only in the quick commissioning

 

 

 

mode (p0010 = 1).

 

 

0x71

Parameter %s [%s]: Write access

 

only in the ready mode (p0010 = 0).

 

 

0x72

Parameter %s [%s]: Write access

 

only in the commissioning state,

 

 

 

parameter reset (p0010 = 30).

 

 

0x73

Parameter %s [%s]: Write access

 

only in the commissioning state,

 

 

 

Safety (p0010 = 95).

 

 

0x74

Parameter %s [%s]: Write access

 

only in the commissioning state, tech.

 

 

 

application/units (p0010 = 5).

 

 

0x75

Parameter %s [%s]: Write access

 

only in the commissioning state

 

 

 

(p0010 not equal to 0).

 

 

0x76

Parameter %s [%s]: Write access

 

only in the commissioning state,

 

 

 

download (p0010 = 29).

 

 

0x77

Parameter %s [%s] may not be

 

written in download.

 

 

Drive Functions

397

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4