Basic information about the drive system 12.7 Examples of replacing components

Action

Reaction

Comments

Set p9905 to "1"

Alarm disappears

The serial number is stored in

 

The serial number is copied

the RAM of the Control Unit and

 

to the target topology

has to be copied to the non-

 

 

volatile memory with p0971 or

 

 

p0977.

The component has been successfully replaced

 

Example: Replacing a Motor Module/Power Module with a different power rating

Precondition:

The replaced power unit has a different power rating

Vector: Power rating of the Motor Module/Power Module not greater than 4 * motor current

Table 12-13 Example: Replacing a power unit with a different power rating

 

 

Action

 

Reaction

Comments

Switch off the power supply

 

 

 

Replace the defective

 

 

 

 

component and connect the

 

 

 

 

new one

 

 

 

Switch on the power supply

Alarm A01420

 

 

 

 

 

Drive Object CU:

 

 

For p9906=2: Caution

 

p0009 = 1

Device configuration

Topology monitoring for all

 

p9906 = 2

Component comparison

(!) components heavily

 

p0009 = 0

Completing the configuration

reduced so that DRIVE-CLiQ

 

p0977 = 1

Data Backup

lines may be hidden by

 

mistake.

 

 

 

 

 

Drive Object component:

 

 

The new order number is

 

p0201 = r0200

Use the code number

stored in the RAM of the

 

p0010 = 0

Completing commissioning

Control Unit and has to be

 

copied to the non-volatile

 

p0971 = 1

Data Backup

 

memory with p0971 or

 

 

 

 

 

 

 

 

 

 

p0977.

The component has been successfully replaced

 