Applications

11.3 Motor changeover

U

U

U

.+ .+

S>@

.

S>@.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

.

 

.

 

 

 

 

 

 

 

 

 

 

.

 

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

.+

 

.+

 

 

 

 

8

 

 

 

 

8

 

 

 

 

.

 

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

 

 

 

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

:

 

 

 

 

:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 11-3 Example: star/delta switchover

 

 

 

 

 

 

 

 

 

Table 11-4 Settings for the example

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

 

 

 

 

Settings

 

 

 

 

 

 

 

Comments

p0130

 

2

 

 

 

 

 

 

 

 

 

 

Configure 2 MDS.

 

 

 

p0180

 

2

 

 

 

 

 

 

 

 

 

 

Configure 2 DDS.

 

 

 

p0186[0..1]

 

0, 1

 

 

 

 

 

 

 

 

The MDS are assigned to the DDS.

p0820

 

p2197.2

 

 

 

 

 

 

Switchover to delta connection after speed in

p0821 to p0824 0

 

0

 

 

 

 

 

 

 

 

 

 

p2155 is exceeded.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

p0826[0..1]

 

0; 0

 

 

 

 

 

 

 

 

Identical numbers signify the same thermal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

model.

 

 

 

p0827[0..1]

 

1, 2

 

 

 

 

 

 

 

 

Assign the bit from p0830 to the MDS. If

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

p0827[0] = 1, for example, bit p0830.1 is set when

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MDS0 is selected via DDS0.

p0830.1 and p0830.2

 

Digital outputs auxiliary

 

The digital outputs for the auxiliary contactors are

 

 

 

 

contactors

 

assigned to the bits.

p0831[0..1]

 

Digital inputs auxiliary

 

The digital inputs for the checkback from the

 

 

 

 

contacts

 

 

 

 

 

 

motor contactors are assigned.

p0833.0..2

 

0, 0, 0

 

 

 

 

 

 

 

 

The drive is responsible for controlling the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

contactor circuit and the pulse inhibit. Parking bit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Gn_ZSW14) is set.

p2155

 

Switchover speed

 

Sets the speed at which the switchover is to be

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

carried out in delta.

Procedure for star/delta switchover

1.Start condition:

For synchronous motors, the actual speed must be lower than the star field weakening speed. This prevents the regenerative voltage from exceeding the terminal voltage.

2.Pulse inhibit:

After selecting a new drive data set using p0820, the pulses are inhibited.

458

Drive Functions

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Page 458
Image 458