Safety Integrated basic functions

9.7 Commissioning the "STO", "SBC" and "SS1" functions

No.

Parameter

Description/comments

8

 

Set transition period from STOP F to STOP A.

 

p9658 = "Value"

Transitional period from STOP F to STOP A on Control Unit

 

p9858 = "Value"

Transitional period from STOP F to STOP A on Motor Module

 

 

The parameters are not changed until safety commissioning mode has been exited

 

 

(i.e. when p0010 ≠ 95 is set).

 

 

STOP F is the fault reaction that is initiated when the data cross-check is violated as a

 

 

result of fault F01611 or F30611 (SI: defect in a monitoring channel). STOP F

 

 

normally triggers "No fault reaction".

 

 

After the parameterized time has expired, STOP A (immediate safety pulse inhibit) is

 

 

triggered by the fault F01600 or F30600 (SI: STOP A triggered).

 

 

The default setting for p9658 and p9858 is 0 (i.e., STOP F immediately results in

 

 

STOP A).

 

 

Both parameters are included in the crosswise data comparison and must, therefore,

 

 

be identical. A difference of one safety monitoring clock cycle is tolerated for the

 

 

values.

9

p9659 = "Value"

Time for carrying out forced dormant error detection and testing the safety switch-off

 

 

paths.

 

 

After this time has expired, the user is requested to test the switch-off paths as a

 

 

result of alarm A01699 (SI CU: Necessary to test the switch-off signal paths) (i.e.

 

 

select/de-select STO).

 

 

The commissioning engineer can change the time required for carrying out the forced

 

 

dormant error detection and testing the safety switch-off paths.

10

 

Adjust specified checksums.

 

p9799 = "r9798"

Specified checksum on the Control Unit

 

p9899 = "r9898"

Specified checksum on the Motor Module

 

 

The current checksums for the Safety parameters that have undergone a checksum

 

 

check are displayed as follows:

 

 

Actual checksum on the Control Unit: r9798

 

 

Actual checksum on the Motor Module: r9898

 

 

By setting the actual checksum in the parameter for the specified checksum, the

 

 

commissioning engineer confirms the Safety parameters in each monitoring channel.

 

 

This procedure is performed automatically when STARTER and the commissioning

 

 

Wizard for SINAMICS Safety Integrated are used.

11

 

Set the new Safety password.

 

p9762 = "Value"

Enter a new password.

 

p9763 = "Value"

Confirm the new password.

 

 

The new password is not valid until it has been entered in p9762 and confirmed in

 

 

p9763.

 

 

As of now, you must enter the new password in p9761 so that you can change Safety

 

 

parameters.

 

 

Changing the Safety password does not mean that you have to change the

 

 

checksums in p9799 and p9899.

322

Drive Functions

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Page 322
Image 322
Efficient Networks S120 manual Stop a, Paths, Adjust specified checksums, Set the new Safety password