Efficient Networks S120 Replacing a device, Data transfer from CompactFlash card to Sensor Module

Models: S120

1 560
Download 560 pages 21.93 Kb
Page 503
Image 503

Basic information about the drive system 12.8 Exchanging a SINAMICS Sensor Module Integrated

12.8.2Replacing a device

Order number SINAMICS Sensor Module Integrated:

SMI10: 6SL3055-0AA00-5NA0

SMI20: 6SL3055-0AA00-5MA0

In the case of spare part installation, transfer the data previously saved on the

CompactFlash card to the new Sensor Module.

Data transfer from CompactFlash card to Sensor Module

1.Enter the component number of the new Sensor Module (p0141) in p4690.

2.Activate the data backup via p4691 = 2.

3.Execute POWER ON for all DRIVE-CLiQ components.

4.Backup the data of all SINAMICS Sensor Modules Integrated with p4692 = 1.

NOTICE

Only consistent compliance with the procedures and with their systematic, complete documentation in the LOGBOOK enables a reproduction of all service steps, extensions or alterations to the drive system.

Supplementary conditions

The Sensor Module files are stored in a block structure. These blocks are placed directly next to each other (internal data of the SINAMICS Sensor Module Integrated encoder block motor block). If a Sensor Module already contains an encoder block and motor block, and these stored blocks are smaller than the blocks that are to be backed up, then the backup is rejected.

Backup is also rejected when only one of the two files is stored on the Sensor Module.

The Sensor Module must be empty before the exchange.

Overview of key parameters (see SINAMICS S List Manual)

p4690 SMI component number

p4691 Backup SMI data

p4692 Backup all SMI data

Drive Functions

503

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Page 503
Image 503
Efficient Networks S120 manual Replacing a device, Data transfer from CompactFlash card to Sensor Module