Function modules 7.3 Extended monitoring functions

7.3.2Commissioning

The extended monitoring functions are activated while the commissioning Wizard is running. Parameter r0108.17 indicates whether it has been activated.

7.3.3Integration

The extended monitoring functions are integrated as follows in the system.

Function diagrams (see SINAMICS S List Manual)

8010 Speed messages

8013 Load monitoring

Overview of key parameters (see SINAMICS S List Manual)

Load monitoring

p2181[D] Load monitoring response

p2182[D] Load monitoring speed threshold 1

p2183[D] Load monitoring speed threshold 2

p2184[D] Load monitoring speed threshold 3

p2185[D] Load torque monitoring torque threshold 1 upper

...

p2190[D] Load torque monitoring torque threshold 3 lower

p2192[D] Load monitoring delay time

Speed setpoint monitoring

p2150[D] Hysteresis speed 3

p2151[C] CI: Speed setpoint

p2161[D] Speed threshold value 3

r2198.4 BO: ZSW monitoring 2, n_setp ≤ p2161

r2198.5 BO: ZSW monitoring 2, n_setp < 0

Drive Functions

225

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4