3.7 Current setpoint filter

Current controller adaptation

p0391[0...n] Current controller adaptation lower starting point

p0392[0...n] Current controller adaptation upper starting point

p0393[0...n] Current controller adaptation upper P gain

p1590[0...n] Flux controller P gain

p1592[0...n] Flux controller integral time

3.7Current setpoint filter

Description

The four current setpoint filters connected in series can be parameterized as follows:

Low-pass 2nd order (PT2: -40 dB/decade) (type 1)

General filter 2nd order (type 2)

Bandstop and lowpass with reduction are converted to the parameters of the general filter 2nd order via STARTER.

Bandstop

Low-pass with reduction by a constant value

The phase frequency curve is shown alongside the amplitude log frequency curve. A phase shift results in a control system delay and should be kept to a minimum.

78

Drive Functions