Communication PROFIBUS DP/PROFINET IO 10.2 Communication via PROFIBUS DP

10.2.4.4Commissioning of the PROFIBUS slave-to-slave communication

The commissioning of slave-to-slave communication between two SINAMICS drives using the additional Drive ES Basic package is described below.

Settings in HW Config

The project below is used to describe the settings in HW Config.

Figure 10-32 Example project of a PROFIBUS network in HW Config

Procedure

1.Select a slave (e.g. CU320) and use its properties to configure the telegram for the connected drive object.

2.In the "Configuration" tab of the drive unit, select e.g. the standard telegram 2 for the associated servo or vector drive in the telegram selection.

426

Drive Functions

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Page 426
Image 426
Efficient Networks S120 manual Commissioning of the Profibus slave-to-slave communication, Settings in HW Config