Basic information about the drive system

12.4 BICO technology: interconnecting signals

Note

Each installed drive object is allocated a number between 0 and 63 during initial commissioning for unique identification.

Overview of key parameters (see SINAMICS S List Manual)

Adjustable parameters

p0101 Drive object numbers

p0107 Drive object type

p0108 Drive object configuration Display parameters

r0102 Number of drive objects

12.4BICO technology: interconnecting signals

12.4.1Description

Description

Every drive contains a large number of interconnectable input and output variables and internal control variables.

BICO technology (Binector Connector Technology) allows the drive to be adapted to a wide variety of conditions.

Digital and analog signals, which can be interconnected as required by means of BICO parameters, are identified by the prefix BI, BO, CI, or CO in their parameter name.

These parameters are identified accordingly in the parameter list or in the function diagrams.

Note

The STARTER parameterization and commissioning tool is recommended when using BICO technology.

12.4.2Binectors, connectors

Binectors, BI: Binector Input, BO: Binector Output

A binector is a digital (binary) signal without a unit which can assume the value 0 or 1.