DEFINITY Enterprise Communications Server Release 8.2
Upgrades and Additions for R8r
555-233-115 Issue 1
April 2000
Upgrading R5si/R6si to R8r EPN and Adding Memory
3-56DEFINITY AUDIX Power Procedures
3
DEFINITY AUDIX Power Procedures
Power Down the AUDIX System
A yellow caution sticker on the syst em’s power unit notifies technic ians to shut
down the DEFINITY AUDIX System prior to powering down the system.
1. Log into the AUDIX System as craft.
2. Type reset system shutdown and press Enter. Press Enter
once
.
NOTE:
Do not press Enter again. This will force the AUDIX to shutdown
immediately, dropping all active calls on the AUDIX.
3. The “SHUTDOWN Completed” message appear s when the AUDIX is
successfully shutdown. This takes about 2 minutes.
4. The AUDIX System can now be removed for service.
Power Up the AUDIX System
If the AUDIX was removed from the cabinet:
1. Re-install the AUDIX and allow it to boot up automatic ally.
2. Check for AUDIX System errors.
If the AUDIX remained in the cabinet bu t power was removed from the
cabinet:
1. Power up the cabinet. The AUDIX reboots automatic ally.
2. Check for AUDIX System errors.
If the AUDIX remained in the cabinet and the cabinet was
not
powered
down:
1. At the AUDIX console, hold the crtl key and type cc.
2. Type 5 at the prompt. In about 2 minutes, the AUDIX boots up.
3. When the system initialization is complete, log in as craft.
4. Check for AUDIX System errors.