Multicarrier G2 Universal Module to R8r EPN
5-57High Reliability
5
For Either 1 or 2 Collocated Expansion Port Networks
1. At control carrier A of PPN cabinet 1 (see Figure 5-15 through Figure
5-18):
■Install a lightwave transceiver on the c able connector at slot 1A01.
NOTE:
Attenuators may be required for single mode fiber using a
300A Lightwave Transceiver
■Connect a fiber optic cable to the transc eiver just installed.
■Carefully attach the fiber optic cable (with ca ble ties) to the wall of
the cable tray at the built- in cable tie positions.
2. Behind control carrier A of EPN cabinet 2:
■Install a lightwave transceiver on the c able connector at slot 2A01.
NOTE:
Attenuators may be required for single mode fiber using a
300A Lightwave Transceiver
■Connect the other end of the fib er optic cab le to the transceiver just
installed.
■Carefully attach the fiber optic cable (with ca ble ties) to the wall of
the cable tray at the built- in cable tie positions.
■At the top of the cabinet, c oil the surplus of fiber op tic cable and
carefully attach the coil to the wall of the cable tray.