Agilent Technologies 5250 user manual SERIAL0 STOPS=, SERIAL0 FLOW=

Models: 5250

1 285
Download 285 pages 12.39 Kb
Page 55
Image 55

19.Press f. The display should read: SERIAL0: STOPS=

20.Press g. The display should read: STOPS= setting

where setting is the default number of stop bits for the alternate host.

21.If the stop bit setting shown is not correct, use d and f to select the proper stop bit setting. When the value is set, press ENTER. The display should scroll to the right to read:

SERIAL0: STOPS=

22.Press f. The display should read: SERIAL0: FLOW=

23.Press g. The display should read: FLOW= setting

where setting is the default flow control setting for the alternate host.

24.If the flow control setting shown is not correct, use d and f to select the proper setting. When the value is set, press ENTER. The display should scroll to the right to read:

SERIAL0: FLOW=

25.Press s. The display will scroll to the left and should read: CONFIG:SERIAL0:

SERIAL I/O PORT 0 is now configured. Unless using the other serial port for alternate host input, move to “Saving the Configuration.”

To configure SERIAL I/O PORT 1 as an alternate host input port, simply repeat this procedure for that port.

Page 55
Image 55
Agilent Technologies 5250 user manual SERIAL0 STOPS=, SERIAL0 FLOW=