Installing DC power Page 103 of 456

remote or local access (PSTN, GSM, EEM, TCP/IP, SNMP)

local and remote Graphical User Interface (GUI) with multi-language compatibility

Distribution 300 panel

The Candeo SP48300 can have either one or two distribution panels. Each distribution panel can support 300 A. The panels are used to connect small and medium capacity distribution loads. They can accommodate a wide variety of distribution hardware in various configurations.

The initial distribution panel supports 18 load feeds and 8 battery feeds, together with Battery Low Voltage Detection (BLVD). The supplementary distribution panel supports an additional 26 load feeds.

Both the initial (main) and supplementary distribution panels provide local fuse and/or circuit breaker alarm indication by means of a red LED indicator.

In addition to providing protection and connecting points for the battery and battery return cables for the loads, the initial distribution panel provides:

a connecting point for the system’s main battery return reference (BRR) cable

connecting points for the bus bar links to bridge the supplementary distribution panel, if provided

connecting points for the bridge cables for a field-installed supplementary rectifier shelf, if provided

connecting points for the interface with the outside world (alarms inputs and outputs, etc.)

an LVD contactor inhibit switch

Battery enclosure for EMEA countries

For EMEA countries, if backup batteries are used, a battery enclosure is required. Individual batteries are Hawker Energy SBS 60 Valve Regulated Lead Acid (VRLA), 12 V DC nominal voltage, with a capacity of 50.8 Ah. They are available in battery modules containing four batteries each (A0669283 Battery Module). Install the modules in the N0003344 Battery

Communication Server 1000M and Meridian 1 Large System Installation and Commissioning

Page 103
Image 103
Nortel Networks 1000M warranty Distribution 300 panel