Installing DC power Page 129 of 456

Connecting UK power to the Four-Feed PDU

To connect the external power system to the pedestal, use the following procedure for each column (this procedure gives the connections for a four-module column).

Note: All wiring to the PDU must be routed within the cable-tie saddles and under the cable restraint bar at the base of the pedestal.

Procedure 10

Connecting UK power to the Four-Feed PDU

1Open the front door of the 8B/2R or 8B/4R master power cabinet.

2If a junction box is used, insert the conduit from the junction box into one of the conduit access holes in the pedestal.

Connect the wires from the junction box to the matching connections on the terminal block on the PDU.

a.Connect the red wires – BAT 0, – BAT 1, – BAT 2, and – BAT 3.

b.Connect the black wires + BATRTN 0, + BATRTN 1, + BATRTN 2, and + BATRTN 3.

c.Connect the remaining LRTN wire (orange or white wire).

Note: If a junction box is used, the connections described in Steps 2 through 4 apply to the junction box rather than the pedestal.

3Connect the red BAT (–48 V) wires.

a.At the 8B/2R or 8B/4R master power cabinet, connect wires to the terminals on the –ve distribution rail (see Figure 46 on page 128).

b.At the PDU, connect the wires to the terminal block.

i.Connect module 0 to – BAT 0.

ii.Connect module 1 to – BAT 1.

iii.Connect module 2 to – BAT 2.

iv.Connect module 3 to – BAT 3.