Installing AC power Page 79 of 456
Figure 25
Single column – ground and logic return distribution
AC input
Large System | Service | ||
|
|
| panel |
|
|
|
Cord or
conduit
208/240 V
receptacle (30 A L6 - 30
or
IG - L6 - 30)
120 V receptacle
IG or ACEG
Logic return
(#6 AWG)
Safety ground (#6 AWG, min)
AC conduit
Note: In an isolated ground system, the dedicated isolated ground bus bar in the service panel serves as the ground window. It is used for all AC safety grounds and logic returns. It also accommodates a conductor that references the (+) battery bus in DC systems.
Communication Server 1000M and Meridian 1 Large System Installation and Commissioning