Adding a module to a column Page 373 of 456
5Connect the power and system monitor cables between modules:
a.Connect the power connectors between the module being added and the modules above and below it.
b.Connect the system monitor cable from connector J2 in the module below to J1 in the module being added (review Figure 127 on page 369).
c.Connect the system monitor cable from J2 in the module being added to J1 in the module above.
6Restore power to the module:
• With AC power, set the main circuit breaker to ON (up) in the rear of the pedestal.
• With DC power, set the circuit breaker in the rear of the pedestal then the module power supply to ON (up) for the module that was added and for any module that was moved.
7Reinstall the system monitor in the pedestal:
a.Reconnect the RJ11 cable to J6, then the cable to J3. Reinstall the system monitor.
b.If the column houses the master system monitor, load LD 37, and software
LD 37 |
|
ENL TTY x | enable the device associated with the port |
**** | exit LD 37 |
8Replace all module covers and the pedestal grill.
End of Procedure
Communication Server 1000M and Meridian 1 Large System Installation and Commissioning