Installing AC power Page 83 of 456

Figure 28

PDU ground lug locations

 

 

 

 

+

+

 

 

 

+

+

 

 

 

+

MAIN

 

 

 

+

CIRCUIT

 

 

 

 

BREAKER

ON

ON

ON

+

+

+

+

+

+

+

 

PDU

 

 

8D53CB

553-8993

Ground lugs

4Connect the safety ground/protective earth wire (insulated ground wire must be used for system grounding).

a.For a single-column system, connect a #6 AWG wire from the ground source in the service panel to a ground lug on the pedestal.

b.For a multiple-column system, connect a #6 AWG wire from the ground source in the service panel to a ground lug on the closest column. Daisy-chain #6 AWG ground wires from one pedestal to the next as illustrated in Figure 29, connecting all of the columns together. You can also run a #6 AWG wire from the ground source to each column individually. If the columns are not bolted together, physically separated groups of columns should be grounded individually as shown in Figure 27 on page 81.

Figure 29

AC column ground lug daisy chain connection

 

 

 

 

+

+

 

 

 

+

+

 

 

 

+

MAIN

 

 

 

+

CIRCUIT

 

 

 

 

BREAKER

ON

ON

ON

+

+

+

+

+

+

+

 

PDU

 

 

8D53CB

 

 

 

 

+

+

 

 

 

+

+

 

 

 

+

MAIN

 

 

 

+

CIRCUIT

 

 

 

 

BREAKER

ON

ON

ON

+

+

+

+

+

+

+

 

PDU

 

 

8D53CB

From

To ground/protective

Terminate on

ground source

earth lug of next column

last column

 

 

553-8992

Communication Server 1000M and Meridian 1 Large System Installation and Commissioning

Page 83
Image 83
Nortel Networks 1000M warranty PDU ground lug locations, AC column ground lug daisy chain connection