Page 134 of 456 Planning and designating a Main Distribution Frame

This chapter describes how to install and connect a CS 1000M system using the BIX or Krone Test Jack Frame (UK) cross-connect terminals.

Note: The examples shown here are BIX and Krone cross-connect systems. These items are commercially available, but are not supplied by Nortel.

This chapter contains the following procedures:

Procedure 11: “Installing the BIX cross-connect terminal” on page 135.

Procedure 12: “Installing the Krone Test Jack Frame (UK)” on page 138.

Terminal block requirements

The cross-connect terminal requires enough connecting blocks to terminate:

up to 16 25-pair cables for each IPE shelf

up to four 25-pair cables for each Media Gateway and Media Gateway Expander

four conductors for the AUX cable from the Media Gateway

one 25-pair cable from each PFTU

wiring from telephones and trunks.

DANGER

Always use caution when installing or modifying telephone lines. Do not install telephone wiring during a lightning storm. Never touch uninsulated telephone wiring, unless the line is disconnected at the network interface.

Installing the BIX cross-connect terminal

Procedure 11 describes how to install the BIX cross-connect terminal.

NN43021-310 Standard 02.01 December 2007