Installing AC power Page 85 of 456

Installing UPS ground cabling

Use the manufacturer’s documents to install and cable a UPS. If the UPS does not contain an integral bypass switch, add one externally during initial UPS wiring. Figure 31 is a block diagram of a UPS installation and associated wiring.

Follow Procedure 5 to install UPS ground cabling.

Note: Because UPS installation can be complex, Nortel recommends that installers attend vendor training programs.

Figure 31

AC reserve power configuration

External power distribution

CS 1000M Large System

AC input

Service

panel

UPS bypass

switch

208/240 V ac

AC/DC DC/AC Converter Inverter

UPS

Receptacle and

cord, or conduit, to

pedestal(s)

Battery bank

(may be inside UPS)

Note: The ac safety ground (green wire) must route from the service

 

panel, through the UPS, to the Large System panel or receptacles.

553-3163A

Communication Server 1000M and Meridian 1 Large System Installation and Commissioning

Page 85
Image 85
Nortel Networks 1000M warranty Installing UPS ground cabling, AC reserve power configuration