Configuring the system monitor Page 167 of 456

Main AC fail

Rectifier fail major (RFA major)

Low voltage disconnect (LVD)

High voltage (HV)

Fuse alarm (FA)

Priority low voltage disconnect

AC input over-voltage

Rectifier AC fail

Remote shutdown

System Manager SP fail

Configuration fail

Battery on discharge (BOD)

Low voltage (LV)

Very high battery temperature

Table 15

System Monitor connections – NT8D46xx

Wire

Connector pins

Colour

Label

Suggested alarm

 

 

 

 

 

1

P1-1

Black

DCON0

Rectifier Fail

 

 

 

 

 

2

P1-2

Red

DCON1

Major

 

 

 

 

 

3

P1-3

White

DCON2

Major

 

 

 

 

 

4

P1-4

Green

DCON3

Major

 

 

 

 

 

5

P1-5

Orange

ALARM

Low Float Voltage

 

 

 

 

 

6-9

Not used

Not used

Not used

Not used

 

 

 

 

 

Communication Server 1000M and Meridian 1 Large System Installation and Commissioning

Page 167
Image 167
Nortel Networks 1000M warranty Alarm